Effect of Cable Joints on Frequency Domain Analysis

verfasst von
Younes Norouzi, S Braun, C Frohne, Sahand Seifi, Peter Werle
Abstract

Because of some transportation and production limitations, HV cables have a limited length and therefore joints are an inevitable part of cable systems. The higher probability of a fault in joints makes them a critical point of any cable system. Their locations could be detected with a Time Domain Reflectometry (TDR) measurement, but the preciseness of the TDR method can be improved. The Frequency Domain Analysis (FDA) method is a frequency domain measurement, but it can also be transformed in the time domain and shows similar, but maybe more sensitive results than TDR.

Organisationseinheit(en)
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
Typ
Aufsatz in Konferenzband
Seiten
288-292
Anzahl der Seiten
5
Publikationsdatum
26.11.2018
Publikationsstatus
Veröffentlicht
Peer-reviewed
Ja
ASJC Scopus Sachgebiete
Elektronische, optische und magnetische Materialien, Elektrotechnik und Elektronik
Elektronische Version(en)
https://doi.org/10.1109/ceidp.2018.8544823 (Zugang: Geschlossen)