Evolution and discharge pattern of creeping discharge at aged oil/pressboard interface

verfasst von
Xin Zhou, Hui Bin Shi, Moritz Kuhnke, Peter Werle, Ernst Gockenbach, H. Borsi
Abstract

The present paper investigates progressive creeping discharge at oil/pressboard interface in power transformer. Using a needle-to-plate electrode configuration, AC constant stress tests were carried out with differently aged pressboard samples. Two distinctly different discharge patterns have been observed, namely chronic creeping discharge and acute creeping discharge. Chronic creeping discharge happens with all pressboard samples, whereas acute creeping discharge happens only with massively-aged pressboard. The results of partial discharge detection, on-line temperature monitoring and gas analysis indicate that the chronic creeping discharge is closely correlated o oil phase, while the acute creeping discharge involves multiple discharge mechanisms. It is also found carbonization crack in pressboard interior is the principal cause of white mark and bubble generation during acute creeping discharge.

Organisationseinheit(en)
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
Typ
Aufsatz in Konferenzband
Seiten
1053-1056
Anzahl der Seiten
4
Publikationsdatum
15.12.2016
Publikationsstatus
Veröffentlicht
Peer-reviewed
Ja
ASJC Scopus Sachgebiete
Elektronische, optische und magnetische Materialien, Elektrotechnik und Elektronik
Elektronische Version(en)
https://doi.org/10.1109/ceidp.2016.7785568 (Zugang: Geschlossen)