New method of determining the mean curve of lightning impulses according to IEC 60060-1
- verfasst von
- Arne P. Brede, Peter Werle, Ernst Gockenbach, H. Borsi
- Abstract
In this contribution a new method for the determination of mean curves of lightning impulses is presented. The method is in accordance with the actual standard IEC 60060-1 and based on mathematical curve fitting using the Least Mean Square (LMS) error as quality criterion and the Gauss-Newton or the Levenberg-Marquardt algorithms in order to solve the nonlinear equations. The presented procedure reproduces measured lightning impulses in a more suitable way than conventional functions and is therefore able to determine mean curves of standard lightning impulses as well as of lightning impulses superimposed by oscillations or overshoots. A comparison of results obtained with the described method and other curve fittings by using the IEC-TDG and measured data produced by a special generating circuit shows that the new method is more favourable.
- Organisationseinheit(en)
-
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
- Externe Organisation(en)
-
SINTEF Energy Research AS
- Typ
- Aufsatz in Konferenzband
- Seiten
- 1.74.S29-1.77.S21
- Publikationsdatum
- 1999
- Publikationsstatus
- Veröffentlicht
- Peer-reviewed
- Ja
- ASJC Scopus Sachgebiete
- Elektrotechnik und Elektronik