Influence of the material conditions on the breakdown behaviour of XLPE-samples at voltages of different shapes

verfasst von
Ernst Gockenbach, G. schiller
Abstract

Breakdown investigations at XLPE model cables were worked out at voltages of different shapes. The breakdown voltages are quite different. The highest breakdown voltage was measured at DC voltage with negative polarity and the lowest at AC voltage with 250 Hz. The DC strength is mostly influenced by the water content. While dry model cables have a very high breakdown strength up to 400 kV/mm, the value of wet model cables is approximately 80% of the former. If the model cables contain water trees, the DC breakdown strength is reduced further. The most sensitive voltage form in order to discover water trees is clearly the 0.1-Hz-AC-Voltage.

Organisationseinheit(en)
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
Typ
Konferenzaufsatz in Fachzeitschrift
Journal
Conference Record of IEEE International Symposium on Electrical Insulation
Band
2
Seiten
608-611
Anzahl der Seiten
4
ISSN
0164-2006
Publikationsdatum
1996
Publikationsstatus
Veröffentlicht
Peer-reviewed
Ja
ASJC Scopus Sachgebiete
Elektrotechnik und Elektronik, Bauwesen