Anwendung eines Fuzzy-Logik-Algorithmus für die Lebensdauerabschätzung von Transformatoren im Betrieb
- authored by
- Sebastian Schreiter, Tobias Kinkeldey, Holger Lohmeyer, Peter Werle, Tobias Münster, K. Hämel, J. Preusel
- Abstract
Transformers belong to the most valuable equipment within the electrical energy supply. It is therefore of fundamental interest for transformer operators to estimate the remaining life time of these apparatus. The average degree of depolarisation (DP value) is used as a measure of ageing, which must, however, be obtained from a paper sample. As these are not accessible during operation, the DP value is often determined using furan derivatives. However, investigations show partly strong deviations from the actual DP values. In this paper, the results of the DP value estimation using a new fuzzy algorithm are therefore presented in comparison to the actual DP values.
- Organisation(s)
-
High Voltage Engineering and Asset Management Section (Schering Institute)
- External Organisation(s)
-
Leipzig University of Applied Sciences
ABB Group
GRIDINSPECT GmbH
- Type
- Conference contribution
- Pages
- 566-569
- No. of pages
- 4
- Publication date
- 2020
- Publication status
- Published
- Peer reviewed
- Yes
- ASJC Scopus subject areas
- Energy Engineering and Power Technology, Electrical and Electronic Engineering