Influence of the material conditions on the breakdown behaviour of XLPE-samples at voltages of different shapes

authored by
Ernst Gockenbach, G. schiller
Abstract

Breakdown investigations at XLPE model cables were worked out at voltages of different shapes. The breakdown voltages are quite different. The highest breakdown voltage was measured at DC voltage with negative polarity and the lowest at AC voltage with 250 Hz. The DC strength is mostly influenced by the water content. While dry model cables have a very high breakdown strength up to 400 kV/mm, the value of wet model cables is approximately 80% of the former. If the model cables contain water trees, the DC breakdown strength is reduced further. The most sensitive voltage form in order to discover water trees is clearly the 0.1-Hz-AC-Voltage.

Organisation(s)
High Voltage Engineering and Asset Management Section (Schering Institute)
Type
Conference article
Journal
Conference Record of IEEE International Symposium on Electrical Insulation
Volume
2
Pages
608-611
No. of pages
4
ISSN
0164-2006
Publication date
1996
Publication status
Published
Peer reviewed
Yes
ASJC Scopus subject areas
Electrical and Electronic Engineering, Building and Construction